Instrumentation & Calibration
4–20 mA Signal Scaling
Convert a measured loop current to percentage of calibrated span and engineering value, or calculate the expected current for a known process value.
Field use
A linear loop check, not a transmitter configuration tool.
Use it to verify expected indication during calibration, loop checks and troubleshooting where the instrument output is linearly scaled from 4 to 20 mA.
Calculation basis
For a linear 4–20 mA output:
Process value = LRV + (% span / 100) × (URV − LRV)
mA = 4 + 16 × ((PV − LRV) / (URV − LRV))
LRV: lower range value.
URV: upper range value.
PV: process value in the selected engineering unit.
Applicability: linear 4–20 mA scaling. Square-root extraction, characterized outputs and device-specific alarm currents require separate treatment. ISA50 documentation continues to identify 4–20 mA as a widely used industrial analog signal; the historical ANSI/ISA-50.00.01 document was archived by ISA in 2024.