Minor Loss / K Coefficient
Calculate local pressure loss through fittings, valves and similar components from a supplied total loss coefficient, or infer an effective K-value from a known pressure loss.
Field use
Add local losses without hiding the coefficient basis.
Useful for elbows, tees, reducers, valves, strainers and similar components after an appropriate K-value has been established from a recognized source or manufacturer.
Calculation basis
h = ΣK · v² / 2g
Local/minor losses are separated from straight-pipe Darcy-Weisbach major loss. Multiple components may be represented by a total ΣK only when their K-values are valid for the selected engineering basis.
Scope: steady, single-phase screening. Excludes compressibility, flashing, multiphase flow, interaction between closely spaced fittings, detailed valve characteristics, and any automatic fitting K-table. Standard-condition gas rate must first be converted to actual line-condition volumetric flow.